Rules

Beyond the JSON Schema, uniwire checks documents against rule profiles. The core rules (including the PLC checks) always run; other profiles are enabled per document with "profiles": [...], or on the command line with --profile.

uniwire check house.uniwire.json                       # core + the document's profiles
uniwire check house.uniwire.json --profile iec60364    # core + iec60364 only
import uniwire
findings = uniwire.check(uniwire.load("house.uniwire.json"), ["nfc15100", "iec60364"])

Note

These rules are consistency checks that help catch mistakes early. They do not replace the applicable standards, nor the verification of an installation by a qualified person.

Findings

Each finding has a level, a stable rule id, the node concerned and a message:

house.uniwire.json: 2 finding(s)
  WARNING nfc15100.rcd-count [Q1]: only one 30 mA residual-current device (dwellings: at least 2; set installation.premises for other premises)
  ERROR   nfc15100.section [Q12]: 25 A breaker on 2.5 mm² (max 20 A)
Level Meaning
error The document contradicts a rule; uniwire check exits with code 1
warning Probably wrong, or a recommendation not met
info Reminder, or a check that could not be completed (data not covered)

In Python, a Finding has the attributes level, rule, message, node and source. Rules based on a standard carry a source (the document and clause the rule relies on) and a confidence (high or medium), available in uniwire.rules.RULE_INFO. Messages are translated: set UNIWIRE_LANG to fr, de, es, pt, it, nl, pl, tr, hr, sr, sr-Cyrl, bs, ru, zh or ja.

An unknown profile name produces a profile warning.

core (always active)

Rule Check Level
core.ref-unique A reference designation is unique within a board (it may repeat across boards) warning
core.symbol-set-unknown The symbol set named in symbols is installed (registered by a package); otherwise the drawing uses the IEC symbols warning
core.symbol-set-error The symbol set loads and each of its symbols draws; otherwise the IEC symbol is drawn instead warning
core.folio-duplicate Two views do not start at the same sheet number (first_folio); the later one is numbered after the sheets before it warning
core.folio-overlap The sheets of a view do not take numbers already given to the views before it (a first_folio inside their range, or a view running into the next one's); it is numbered after them. Known only once every view is drawn: reported with the PDF of every view (page "About this document", uniwire render), not by check warning
core.rating-cascade A breaker, RCBO or fuse does not have a higher rating than the protective device directly upstream warning
core.transfer-target A transfer link ends on a transfer_switch error
core.transfer-source A transfer switch receives a second source (transfer link) warning
core.tie-device A tie link describes its coupling device info
core.scope The document describes control circuits (contactors or relays fed by a control power supply and switching nothing, coils, push buttons or signal lamps entered as loads): uniwire draws power distribution, not control schematics, so they are only summarized info
core.phases-feeder A three-phase load (phases: 3) is fed by a circuit with three phases: not by a single-phase one (1P+N or 2P protection, 3G cable, single-phase supply); a drive or a converter in between makes its own phases warning
core.view-direction A view asks for a left-right drawing (direction right or left): it is drawn top-down, left-right drawing is not available yet info
core.neutral-missing A device with a neutral pole (1P+N, 3P+N) is on a network that has no neutral (system 3P or 2P, declared on the device, a board, a source or the installation, and not made by a transformer or converter in between) warning
core.system-missing A supply system is declared (system of the installation, a source or a board): without one the number of conductors drawn is inferred from the devices, not stated. Not asked when every source is DC (battery, PV array) info
core.pen-split-missing A TN-C-S installation says at which board the PEN is split into PE and N (pen_split, or a board declaring its own earthing); otherwise both drawings split it at the first board info
core.symbol-text Generic loads (load) and controllers give a symbol_text: their boxes are drawn empty or generic, never with a text guessed from the label. One finding lists them all info
core.load-current The current of a load (p_kW per item: count items of a load add up, a protection with count stands for that many circuits each feeding the load; cos_phi when given) is not more than 10% above the rating of the overcurrent protection that feeds it alone, on the same network (no converter, drive or starter in between), at the voltage of the load (un_V) or of the network of its protection (board, source, transformer secondary, installation); where a circuit may be single-phase or between two phases, at the higher voltage; DC circuits only with the load's un_V warning
core.terminal-node PV arrays, batteries, SPDs and earth electrodes feed nothing (a battery root of sources, the only source of a DC system, may) warning
core.normalized A near-miss value was read in its canonical form on load: poles: 2 as "2P", cable.cores: 3 as "3G", "3G2.5" as "3G" plus section_mm2: 2.5, a [15, 45] range as "15-45", a view type/single_line as kind/single-line, meta.description as a note, revision columns rev, by, note as index, author, description, PLC module kinds written in full (digital_input as di, analog_output as ao), a whole number written for a quoted choice as that choice (EV charger mode: 3 as "3"), an unknown field given null left out, a number written for a text as that text, a text too long for symbol_text without its spaces, else as its initials ("Air conditioner" as "AC"), else as its first whole words that fit, never cut in the middle of a word (a single word too long is cut with a full stop: "Ventilation" as "Venti."), and in an object a single unknown field beside a single missing required one under the missing name. Ambiguous values are not guessed: validation rejects them, and lists only the problems left once the values above are read (a misnamed field is read under the missing name only when the whole document is then valid). uniwire normalize writes the canonical form warning
core.interlock Nodes and links sharing a locks key: no more members closed in normal operation than the interlock has keys (SPEC §4.1); a declared interlock is used by at least 2 members; an undeclared lock is not alone error / warning
core.no-profile Only the core rules ran (no rule profile applied, or installation.standard names a standard no profile covers): the protections, cables and RCDs were not checked, so an empty result does not mean the installation is right info
core.no-cables A profile that checks cables is active (nfc15100, vde0100, iec60364) but no circuit gives its cable size: the cables were not checked, so an empty result does not mean they are right info

PLC rules (part of core)

Modular PLCs (plc) are checked whenever they appear in a document.

Rule Check Level
plc.slots Module slots are unique (error) and in increasing order (warning) error / warning
plc.port A link port (from_port / to_port, "slot.channel") is readable, targets an existing slot and a channel within the module's channel count error
plc.port-shared One output channel does not control several devices warning
plc.coil A 24 V digital output does not drive a coil of a much higher voltage (e.g. 230 V) without an interposing relay warning
plc.wago-end A WAGO local bus ends with an end module (750-600) warning
plc.wago-feed A WAGO controller declares a potential feed module info

nfc15100: French low-voltage installations

Checks of a French low-voltage installation under NF C 15-100, which covers every kind of premises. The version that gives presumption of conformity (order of 3 August 2016, art. 4) is the 2002 edition with its 2005 update and amendments A1 to A5; for dwellings, part 10-1 of amendment A5 (June 2015) replaces the former parts 7-771 and 7-772. The rules of dwellings (marked dwelling) apply when installation.premises is dwelling or not set. For other premises (commercial, office, industrial, public, agricultural, other) only the general rules apply, and the residential cable table becomes a warning to size the cable for its installation method (part 5-52, guide UTE C 15-105).

Rule Check Level
nfc15100.section Copper cross-section ↔ rating: 1.5 → 16 A, 2.5 → 20 A, 4 → 25 A, 6 → 32 A (table 10-1F); outside dwellings, a warning to check the cable for its installation method error (dwelling) / warning
nfc15100.circuit-section Dwelling. Minimum section and maximum protection of dedicated circuits (table 10-1F): washing machine, dishwasher, dryer, oven, water heater 2.5 mm² and 20 A; single-phase cooking 6 mm² and 32 A; three-phase cooking 2.5 mm² and 20 A; 16 A EV charging 2.5 mm² and 20 A; roller shutters 1.5 mm² and 16 A error
nfc15100.points Dwelling. Points added up per circuit: lighting at most 8; 16 A sockets at most 8 on 1.5 mm², 12 on 2.5 mm² (10.1.3.2.3, 10.1.3.3.3) error
nfc15100.lighting-rating Dwelling. Lighting protected at 16 A at most (table 10-1F) error
nfc15100.rcd-30mA 30 mA protection of every final circuit of a dwelling, single-phase or three-phase (order of 3 August 2016, 10.1.4.7.3.1); in all premises, socket-outlets up to 32 A (411.3.3, A4) and EV charging points error
nfc15100.rcd-type-A Type A (not AC) for cooker / hob, washing machine and EV charging circuits (table 10-1G rule 2) error
nfc15100.rcd-count Dwelling. At least 2 30 mA RCDs, single-phase or three-phase (table 10-1G rule 1) error
nfc15100.rcd-circuits Dwelling. At most 8 circuits per 30 mA RCD, counted down to the next RCD, through combs and boards (table 10-1G rule 3) error
nfc15100.rcd-rating Dwelling. Rated current of a 30 mA RCD at least the current of the service breaker (from the subscribed power when known), or 1 × its heating, water heater and EV circuits + 0.5 × the others (table 10-1G rule 4) warning
nfc15100.rcd-spread Dwelling. Lighting circuits on at least 2 RCDs, socket-outlet circuits too (table 10-1G rule 5) error
nfc15100.heating Dwelling. Heating power per circuit (p_kW per item, times count): 3.5 / 4.5 / 5.75 / 7.25 kW at 16 / 20 / 25 / 32 A (table 10-1B) warning
nfc15100.dedicated-circuit Dwelling. Dedicated circuits: washing machine, dishwasher, dryer, oven, hob, water heater, EV charging (one load per circuit), heating and shutters (circuit reserved for that use); freezer recommended (10.1.3.4) error (freezer: warning)
nfc15100.neutral-pole Dwelling. No 1P breaker on a circuit with a neutral: every circuit is isolated on all its live conductors (10.1.4.7.1.1) error
nfc15100.spd-rcd Dwelling. The surge protective device at the origin is not behind a 30 mA RCD (10.1.4.7.3.1) error
nfc15100.agcp-rcd Dwelling, limited-power supply. Service breaker and intermediate RCDs at 500 mA at most, without adjustable sensitivity (10.1.2.2.1) error
nfc15100.supply-section Dwelling. Copper link from the service breaker to the main board: 10 mm² at 30 and 45 A, 16 mm² at 60 A, 25 mm² at 90 A (table 10-1D) error
nfc15100.selectivity A residual-current device with other RCDs downstream is selective (type S): error in a dwelling (10.1.2.2.1), warning elsewhere (535.4.3.1) error / warning
nfc15100.earth-resistance TT: earth electrode resistance × highest RCD sensitivity ≤ 50 V, i.e. 100 Ω with a 500 mA service breaker (411.5.3) error
nfc15100.ev-rcd EV charging: type B in three-phase mode 2 (error); in mode 3 with a type A or F, reminder of 6 mA DC detection (info). Source: IEC 60364-7-722 / guide UTE C 15-722, not part of the 2002 edition and its amendments error / info

vde0100: German low-voltage installations

DIN VDE 0100 is the German adoption of IEC 60364, with the same part numbers. The profile checks the German requirements that go beyond the general rules; combine it with iec60364 for the current-carrying capacity of cables. Dwelling rules apply when installation.premises is "dwelling" or not set.

Rule Check Level
vde0100.rcd-30mA Socket-outlet circuits up to 32 A protected by an RCD of at most 30 mA, all premises (DIN VDE 0100-410:2018, 411.3.3); lighting circuits of dwellings, the same (411.3.4) error
vde0100.bathroom Every circuit of a room with a bath or a shower protected by an RCD of at most 30 mA, except a circuit supplying only a permanently connected water heater (DIN VDE 0100-701). The room is read from the load's room or label (Bad, Badezimmer, Dusche...) error
vde0100.ev-circuit Each charging point supplied by its own final circuit and protected by its own RCD of at most 30 mA (DIN VDE 0100-722) error
vde0100.ev-rcd RCD of a charging point: type AC or not stated (error); type A or F, reminder that the charging point must include 6 mA DC fault detection, RDC-DD, IEC 62955 (info) error / info
vde0100.spd No surge protective device in the installation: required for most buildings (DIN VDE 0100-443 and -534, 2016) warning
vde0100.pen-section A cable whose conductors include a PEN: at least 10 mm² copper or 16 mm² aluminium (DIN VDE 0100-540, 543.4) warning

Not checked: arc fault detection devices (DIN VDE 0100-420, required in some premises only), the connection rules of VDE-AR-N 4100 (meter cabinet, selective main circuit breaker) and the minimum equipment of dwellings (DIN 18015-2). The rules were written from the structure of the standard, without its text: report any difference with the edition you apply.

iec60364: current-carrying capacity and 30 mA RCDs

iec60364.iz

The rating of the protective device feeding a cable (ir_A, otherwise fuse_A, otherwise in_A) must not exceed the cable's current-carrying capacity Iz (multiplied by parallel).

  • Applies when the cable specifies section_mm2, material, insulation and install.
  • Coverage: copper and aluminium, PVC or XLPE (PR and EPR are treated as XLPE); installation methods A1, A2, B1, B2, C, D1 (in a duct in the ground, also written D-duct), D2 (buried directly), E, F, with 2 or 3 loaded conductors, in the cross-sections the IEC tables give (1.5 to 300 mm², from 2.5 mm² for aluminium, from 25 mm² for F). Combinations outside them produce an info.
  • Iz: formulas a * S^m after IEC 60364-5-52, never above its values. Reference conditions: 30 °C in air, 20 °C and 2.5 K·m/W in the ground.
  • Ambient temperature: the cable's ambient_C corrects Iz by sqrt((θmax − θ) / (θmax − θref)), θmax 70 °C for PVC and 90 °C for XLPE, from 10 °C (colder is taken as 10 °C) up to 60 °C for PVC and 80 °C for XLPE; above, Iz is not checked (info). Without ambient_C: 40 °C in air and 20 °C in the ground, and the message says it.
  • Loaded conductors: 3 when the protective device is 3P, 3P+N or 4P, otherwise 2; without poles, installation.system decides.
  • Grouping: grouped (circuits or multicore cables laid together, this one included) applies the grouping factor, in air by arrangement (bunched when not given, single_layer, ceiling, perforated_tray, ladder; with supports, 2 or 3 trays or ladders stacked, grouped counting the cables on one of them), in the ground by spacing_m (0 when not given; single-core cables in their own ducts when cores reads 1x). Up to 20 circuits in air, 9 per stacked support, 6 in the ground.
  • Soil: soil_resistivity_K_m_W corrects Iz in the ground (D1, D2) from 0.5 to 3 K·m/W (a lower value is taken as 0.5).
  • Harmonics: third_harmonic_pct on a three-phase circuit with a neutral (3P+N, 4P, or the system when the poles are not given) multiplies Iz by 1 / sqrt(1 + 4 h²), the heating of the phases and of a neutral carrying their third harmonics, up to 50 %; by 1 / sqrt(1 + 7 h²) up to 15 % when the neutral is smaller.
  • The applied factors are listed in the message. Beyond the range of a factor, Iz is not checked (info).
  • Level: warning, never error. The formulas of Iz and of the factors are in src/uniwire/registry/data/iz_iec60364.json, never above the values of IEC 60364-5-52, read with uniwire.registry.iz_iec60364().

iec60364.iz-estimate

A cable that gives section_mm2 but not its material, insulation or install is not left unchecked:

  • Iz is estimated with copper and PVC unless stated, and the most favourable installation method in air (A1 to F) unless install is given, at 30 °C, or corrected as for iec60364.iz when ambient_C is given, with the grouping, soil and harmonic factors of iec60364.iz.
  • A protection above that Iz is too high under these assumptions: warning, with the assumptions in the message.
  • One info finding lists the cables estimated: give their material, insulation and installation method for the exact check of iec60364.iz.

iec60364.rcd-30mA

IEC 60364-4-41:2005+AMD1:2017, 411.3.3 and 411.3.4: additional protection by an RCD of at most 30 mA (error when missing; the 2005 edition without its amendment stopped at socket-outlets up to 20 A):

  • socket-outlets up to 32 A (their own rating, otherwise the rating of their protection), in all premises;
  • lighting circuits when installation.premises is dwelling.

Not applied below an isolation transformer (kind: "isolation") feeding an IT system (earthing: "IT"): a medical IT system (IEC 60364-7-710) is monitored by an insulation monitoring device instead. When the document also declares nfc15100 or vde0100, this rule leaves the check to them (their national rules go further).

See the specification §10 for the data source and its limitations.

enedis: connection to the French public network

Checks of the connection of a low-voltage installation to the public network operated by Enedis: service cable, meter and service main breaker (AGCP). They follow NF C 14-100 and the Enedis technical reference, not NF C 15-100, which starts downstream of the AGCP; combine the profile with nfc15100 for the installation itself. It applies only when the installation is supplied in low voltage by a grid source (no transformer, un_V up to 1000 V). Enedis decides on each connection: these are consistency checks of the document.

Rule Check Level
enedis.connection Limited-power connection: at most 12 kVA in single-phase (3 to 12 kVA, from 6 kVA in dwellings), 6 to 36 kVA in three-phase; monitored power from 37 to 250 kVA (info); medium voltage above 250 kVA (warning). Source: Enedis-NMO-RAC_001E §3.1 error / warning / info
enedis.agcp-setting Limited power: the AGCP setting (in_A of the main_breaker, range_A being its range) carries the connection power, 60 A for 12 kVA single-phase or 36 kVA three-phase, so 0.2 kVA per ampere single-phase and 0.6 kVA per ampere three-phase. Error when it exceeds 60 A or carries less than installation.subscribed_kVA. Source: Enedis-NMO-RAC_001E §4.1 error
enedis.agcp-rcd AGCP without residual-current protection, or other than 500 mA: NF C 14-100 recommends 500 mA in new buildings (SéQuélec fiche n°2). Type S is checked by nfc15100.selectivity info
enedis.production Production and storage inverters (p_kVA × count: PV, hybrid and battery inverters; chargers, which only draw, are not counted): in single-phase, injection limited to 6 kVA (warning) and installed power to 18 kVA (error); in three-phase, 250 kVA (info above 36 kVA: injection beyond it follows another connection procedure). The installed power includes storage. Sources: Enedis-NMO-RAC_001E §3.2.1, Enedis-NMO-RES_032E §1.2.1.2 error / warning
enedis.service-cable Individual service cable (the cable of the connection meter, from the CCPI): at most 30 m and 35 mm² aluminium (2 x 35 single-phase, 4 x 35 three-phase), for a voltage variation within 2 %. Source: Enedis-NMO-RAC_001E §4.1.3 warning
enedis.decoupling Production or storage inverter without its decoupling protection (protection, e.g. NF EN 50549-1 / NF EN 50549-10), mandatory in every case. Sources: Enedis-NMO-RES_032E §1, Consuel, decoupling protections of PV inverters (2025) info

With the Linky meter, the AGCP is set to the connection power and the meter follows the subscribed power: an AGCP set above the subscribed power is normal, one set below it is an error.

Writing a rule

Rules are plain generator functions registered on a profile:

from uniwire.rules import Finding, rule

@rule("myprofile")
def no_unlabelled_loads(doc, idx):
    for node_id, node in idx.nodes.items():
        if node.type == "load" and not node.label:
            yield Finding("warning", "myprofile.load-label", "load without a label", node_id)

Once the module defining it is imported, "profiles": ["myprofile"] enables it. Rules contributed to the project must translate their messages through uniwire.i18n and come with tests.